INPUT PARAMETERS
Frequency Range 40Hz - 70Hz (50Hz/60Hz auto sensing)
Phase Single phase with ground
Power Factor ≥ 0.99 @ 220 to 230 VAC (input voltage)
VOLTAGE RANGE
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC
High Line Transfer 300 VAC ± 5%
OUTPUT PARAMETERS
Output Voltage 208/220/230/240VAC
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range 47 to 53 Hz or 57 to 63 Hz (Auto Sensing)
Frequency Range (Batt. Mode) 50 Hz ± 0.25Hz
Overload 100% to 110%: audible warning 110% to 130%: UPS shuts down in 30
seconds at battery mode or transfers to bypass mode when the utility
is normal. >130%: UPS shuts down immediately at battery mode or
transfer to bypass mode when the utility is normal.
Current Crest Ratio 3:1
Harmonic Distortion ≤ 3 % THD (Linear Load)
≤ 6 % THD (Non-linear Load)
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode ~ 88%
Battery Mode ~ 83%
TRANSFER TIME
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
BATTERY CHARGER (STANDARD MODEL)
Battery Type 12 V /7 AH 12 V / 9 AH
Numbers 6
Typical Recharge Time 4 hours recover to 90% capacity (Typical)
Charging Current 1.0 A(max.)
Charging Voltage 41.0 VDC ± 1% 82.1 VDC ±1%
BATTERY CHARGER (LONG BACK-UP MODEL)
Number 3 8
Charging Current 4.0 A or 8.0 A(max.)
Charging Voltage 41.0 VDC ±